Division 1 REQUIREMENTS FOR ENERGY EFFICIENCY

United Kingdom

Original text. Later amendments are not shown.

  1. (a)

    From 1 July 2016, the coefficient of performance (COP) and the seasonal energy performance ratio (SEPR) of condensing units shall not fall below the following values:

    Operating temperatureRated capacity PA Applicable ratioValue
    Medium0,2 kW≤ PA ≤ 1 kWCOP1,20
    1 kW< PA ≤ 5 kWCOP1,40
    5 kW < PA ≤ 20 kWSEPR2,25
    20 kW < PA ≤ 50 kWSEPR2,35
    Low0,1 kW≤ PA ≤ 0,4 kWCOP0,75
    0,4 kW< PA ≤ 2 kWCOP0,85
    2 kW < PA ≤ 8kWSEPR1,50
    8 kW < PA ≤ 20 kWSEPR1,60
  2. (b)

    From 1 July 2018, the coefficient of performance (COP) and the seasonal energy performance ratio (SEPR) of condensing units shall not fall below the following values:

    Operating temperatureRated capacity PA Applicable ratioValue
    Medium0,2 kW≤ PA ≤ 1kWCOP1,40
    1 kW< PA ≤ 5 kWCOP1,60
    5 kW < PA ≤ 20 kWSEPR2,55
    20 kW < PA ≤ 50 kWSEPR2,65
    Low0,1 kW≤ PA ≤ 0,4 kWCOP0,80
    0,4 kW< PA ≤ 2 kWCOP0,95
    2 kW < PA ≤ 8 kWSEPR1,60
    8 kW < PA ≤ 20 kWSEPR1,70
  3. (c)

    For condensing units intended to be charged with a refrigerant fluid with a global warming potential lower than 150, COP and SEPR values can be lower than the values indicated in point 1(a) by a maximum of 15 % and in point 1(b) by a maximum of 10 %

  4. (d)

    Condensing units capable of operating both at medium and low temperature shall comply with the requirements of each category for which they are declared.