Division 1 REQUIREMENTS FOR ENERGY EFFICIENCY
United Kingdom
- (a)
From 1 July 2016, the coefficient of performance (COP) and the seasonal energy performance ratio (SEPR) of condensing units shall not fall below the following values:
Operating temperature Rated capacity PA Applicable ratio Value Medium 0,2 kW≤ PA ≤ 1 kW COP 1,20 1 kW< PA ≤ 5 kW COP 1,40 5 kW < PA ≤ 20 kW SEPR 2,25 20 kW < PA ≤ 50 kW SEPR 2,35 Low 0,1 kW≤ PA ≤ 0,4 kW COP 0,75 0,4 kW< PA ≤ 2 kW COP 0,85 2 kW < PA ≤ 8kW SEPR 1,50 8 kW < PA ≤ 20 kW SEPR 1,60 - (b)
From 1 July 2018, the coefficient of performance (COP) and the seasonal energy performance ratio (SEPR) of condensing units shall not fall below the following values:
Operating temperature Rated capacity PA Applicable ratio Value Medium 0,2 kW≤ PA ≤ 1kW COP 1,40 1 kW< PA ≤ 5 kW COP 1,60 5 kW < PA ≤ 20 kW SEPR 2,55 20 kW < PA ≤ 50 kW SEPR 2,65 Low 0,1 kW≤ PA ≤ 0,4 kW COP 0,80 0,4 kW< PA ≤ 2 kW COP 0,95 2 kW < PA ≤ 8 kW SEPR 1,60 8 kW < PA ≤ 20 kW SEPR 1,70 - (c)
For condensing units intended to be charged with a refrigerant fluid with a global warming potential lower than 150, COP and SEPR values can be lower than the values indicated in point 1(a) by a maximum of 15 % and in point 1(b) by a maximum of 10 %
- (d)
Condensing units capable of operating both at medium and low temperature shall comply with the requirements of each category for which they are declared.