Paragraph 3 MPEsF1

The effects of the various measurands and influence quantities (a, b, c,…) are evaluated separately, all other measurands and influence quantities being kept relatively constant at their reference values. The error of measurement, that shall not exceed the MPE stated in Table 2, is calculated as:

When the meter is operating under varying-load current, the percentage errors shall not exceed the limits given in Table 2.

Table 2

Operating temperaturesOperating temperaturesOperating temperaturesOperating temperatures
MPEs in percent at rated operating conditions and defined load current levels and operating temperature
Operating temperaturesOperating temperaturesOperating temperaturesOperating temperatures
+ 5 °C … + 30 °C

– 10 °C … + 5 °C

or

+ 30 °C … + 40 °C

– 25 °C … – 10 °C

or

+ 40 °C … + 55 °C

– 40 °C … – 25 °C

or

+ 55 °C … + 70 °C

Meter classABCABCABCABC

Single phase meter; polyphase meter if operating with balanced loads

Imin ≤ I < Itr3.52152.51.373.51.7942
Itr ≤ I < Imax3.5204.52.5173.51.3941.5

Polyphase meter if operating with single phase load

Itr ≤ I < Imax

, see exception below

42.51531.3741.794.52
For electromechanical polyphase meters the current range for single-phase load is limited to 5Itr ≤ I ≤ Imax

When a meter operates in different temperature ranges the relevant MPE values shall apply.

The meter shall not exploit the MPEs or systematically favour any party.