Paragraph 4.2 Effect of disturbances of long durationF1

Table 3

Critical change values for disturbances of long duration
DisturbanceCritical change values in percent for meters of class
ABC
Reversed phase sequence1.51.50.3
Voltage unbalance (only applicable to polyphase meters)421
Harmonic contents in the current circuits10.80.5
DC and harmonics in the current circuit631.5
Fast transient bursts642
Magnetic fields; HF (radiated RF) electromagnetic field; Conducted disturbances introduced by radio-frequency fields; and Oscillatory waves immunity321

In the case of electromechanical electricity meters, no critical change values are defined for harmonic contents in the current circuits and for DC and harmonics in the current circuit.