Paragraph 5 I1
Northern Ireland
Where a transformer intended for use with a meter has been tested, a statement shall be included in the report that—
the transformer referred to in the report is accurately described and whether it is a new or used transformer;
the uncertainty of measurement was not greater than plus or minus 0.1%;
no transformer error was greater than plus or minus 0.5% at any load from 5% to 120% of full load when connected to the maximum rated burden or, if known, the working burden
Annotations
Commencement
- I1
Sch. 2 para. 5 in operation at 1.2.1999, see reg. 1
Footnotes
- f1
-
Harmonisation Document 553 S2 entitled “Current transformers” has been adopted in the United Kingdom as BS 7626 entitled “Specifications for current transformers” published by the British Standards Institution (ISBN 0 580 21575 X) and was effective from 15th November 1993
- f2
-
Harmonisation Document 554 S1 entitled “Voltage transformers” has been adopted in the United Kingdom as BS 7625 entitled “Specification of voltage transformers” published by the British Standards Institution (ISBN 0 580 21573 3) and was effective from 15th February 1993