Paragraph 2 Non-registration testI1

Northern Ireland

Induction meters

(1)

Induction meters shall be tested to ensure that when the current circuits are open and a voltage of 110% of the marked voltage is applied to the voltage circuits, rotors cease to rotate before completing one revolution.

Static meters

(2)

Static meters shall be tested for non-registration by one of the following methods—

Method 1

(a)
(i)

When subjected to the test conditions specified in paragraph 2(1), the meter shall not emit more than one output pulse over the minimum test period determined in paragraph (ii);

(ii)

the minimum test period (t) shall be computed by the formula:

t ge;480×106k.m.V.Imminutes

where:

  • k = number of pulses per kWh emitted by the meter

  • m = number of elements

  • V = declared system voltage

  • Im = marked maximum current.

Method 2

(b)

When static meters are fitted with inhibiting circuits, they may be tested for non-registration with a current, which is less than the threshold current in respect of a meter of that type, applied to the current circuits and a voltage of 100% of the marked voltage applied to the voltage circuits of the meters under test. Meters shall not emit more than one output pulse over a minimum test period (t) determined as follows—

t=126000V×I×k×pfminutes

where:

  • V = declared system voltage

  • I = total current of all phases

  • k = number of pulses per kWh emitted by the meter

  • pf = power factor.