OpenLegislation

Paragraph 5

The points of discharge of urban waste water shall be chosen, as far as possible, so as to minimise the effects on receiving waters.

TABLE 1

REQUIREMENTS FOR DISCHARGES FROM URBAN WASTE WATER TREATMENT PLANTS SUBJECT TO REGULATION 5(1) AND (2)

The values for concentration or for the percentage of reduction shall apply.

{s001} Reduction in relation to the load of the influent.

{s002} The parameter can be replaced by another parameter: total organic carbon (TOC) or total oxygen demand (TOD) if a relationship can be established between BOD5 and the substitute parameter.

ParametersConcentrationMinimum percentage of reduction {s001}Reference method of measurement
Biochemical oxygen demand (BOD5 at 20°C without nitrification {s002}25 mg/l O270—90Homogenized, unfiltered, undecanted sample. Determination of dissolved oxygen before and after five-day incubation at 20°+1°C, in complete darkness. Addition of a nitrification inhibitor
Chemical oxygen demand (COD)125 mg/l O275Homogenized, unfiltered, undecanted sample Potassium dichromate