OpenLegislation

Article 12 Rate-of-change-of-frequency withstand capability

United Kingdom

Original text. Later amendments are not shown.

An HVDC system shall be capable of staying connected to the network and operable if the network frequency changes at a rate between – F12.5 and + 2.5 Hz/s (measured at any point in time as an average of the rate of change of frequency for the previous 1 s).

Annotations

Textual amendments

F1

Word in Art. 12 substituted (31.12.2020) by The Electricity and Gas (Internal Markets and Network Codes) (Amendment etc.) (EU Exit) Regulations 2020 (S.I. 2020/1006), reg. 1(2), Sch. 3 para. 10