Paragraph 18 Control of noise during operational phaseI1
England, Wales and Scotland
The combined noise rating level from the electrical transmission station, converter and associated plant, emitted during normal operation, shall not exceed 35 dB LAr,Tr at any residential property. The definition of rating level shall be as described in BS 4142:1997. The noise limit only applies to residential properties that have planning permission on 30th July 2013.
Annotations
Commencement
- I1
Sch. 1 Pt. 3 para. 18 in force at 31.12.2014, see art. 1