Paragraph 6 Test loadsI1

England, Wales and Scotland

(1)

Every repaired meter shall be tested at each of the loads specified in table 2, except that test number 2 in that table may be omitted.

(2)

Every new meter shall be calibrated and tested at a sufficient number of load points so as to ensure that meter errors are not greater than the limits specified in paragraph 9.

(3)

A test for starting shall also be carried out on new meters in accordance with test number 7 of table 2.

(4)

The ratio errors shall be determined for voltage transformers that are intended for use with meters but are not tested with a meter.

(5)

Current transformers intended for use with meters but not tested with a meter shall be tested from 5 per cent. to 120 per cent. of rated current.