Paragraph 7 Multi-register metersI1
Northern Ireland
Induction meters
All induction meters with more than one register shall be tested on one register in accordance with paragraphs 5 and 6 and on each and every other register at a low load using Method A, Method B or Method C tests and at a high load using Method A test.
For the same load conditions the maximum permitted difference between the error on one register (expressed as a percentage) and the error on any other register (expressed as a percentage) is one.
Static meters
All static meters with more than one register shall be tested on one register in accordance with paragraphs 5 and 6.
For repaired meters with more than one register —
where the total units are the sum of all the registers, a further test shall be carried out on each and every other register using Method A but
where the total units are recorded on one register, only that register is required to be tested in accordance with paragraphs 5 and 6.